Seamlessly integrate heat pumps, domestic hot water heaters, and swing tanks.

Hybrid systems prioritize flexibility, resilience, and peak performance while all‑electric systems prioritize maximum decarbonization and code alignment. There’s no universal “winner”. The right choice depends on a variety of application-specific factors such as load profile, climate, infrastructure, utility rates, and owner risk tolerance.

A hybrid gas + heat pump DHW plant delivers:
  • Lower operating costs
  • Reduced carbon emissions
  • High peak capacity without oversizing
  • Fuel diversity and resilience
  • Easier retrofits and future flexibility

System Overview

  • Runs heat-pump-only or hybrid HP/gas water heater plants from a single controller
  • Automatically balances installed cost, operating cost, and carbon reduction
  • Coordinates the full HeatNet ecosystem – Transom heat pumps, HeatNet gas water heaters, and swing tanks – over one communication layer
  • Guided hybrid-system configuration in place of field-programmed logic
  • Application flexibility – supports DHW systems with multi-sensor stratified tanks, single-sensor storage tank, and system return/system supply configuration
Interface
  • 10.1″ capacitive touch display
  • HeatNet-networked – up to 16 devices
  • Dual-key locking enclosure with USB service port
  • Enclosure: 16″W x 20″L x 7″D
  • 120VAC, 5A input power

On The Display

Home Screen – Swing Tank

Every input, output, and relay state exposed for fast troubleshooting – gated behind five levels of password-protected access.

System Configuration

Guided setup for hybrid mode, swing tank control, and sanitize scheduling. Supports multi-sensor stratified tanks or single-sensor storage/return/supply.

Diagnostics

Every input, output, and relay state exposed for fast troubleshooting – gated behind five levels of password-protected access.

Thermal Network
  • Up to 16 devices: Transom heat pumps + HeatNet gas water heaters
  • Devices staged by runtime for even equipment wear
  • N+1 gas water heater feature for redundancy
  • HeatNet or 3rd party swing tanks supported
Hybrid Prioritization
  • Heat pumps run first; gas water heaters supplement under high load
  • Switchover triggers on outdoor air temp or high return water temp
  • Tunable to local energy rates to minimize operating cost
  • Reduces cycling on higher-value heat pump equipment
Sanitize Mode
  • Swing tank raises system-wide temperature to control bacteria
  • Scheduled, or activated manually from the display or BMS
Full Recovery Mode
  • Swing tank recharges stratified tanks when HPs can’t keep pace with demand
  • Scheduled, or activated manually from the display or BMS
Communications
  • Native Modbus RTU – BACnet IP and BACnet MS/TP supported with optional bridges
  • Planned: CTA-2045B smart grid connectivity for utility demand response
  • Planned: remote monitoring

Economic Carbon Reduction, By Design